收藏本页 nin好,huanying来dao上hai傲世皇朝3,傲世皇朝3xia载jiang竭诚为nin服务!    工作时间:上午 9:00 - xia午 18:00 温xin提示:
EHS 网站
热门搜索:
fanghuo柜、安全柜、化学品柜、工业安全suo具、sheng漏托pan、吸附棉套装等工业安全yu环保产品;实验台、实验室jia具、通feng柜、实验柜等实验室设ji规划、生产、安装及配件;li心ji、fang爆工具、烘箱、超声波清洗ji、水质监ce仪器及实验蕐e牟牡裙?大类产品。
产品分类
品牌专区 >>更duo
fang溢漏托panUltraTech,Spill Prevention, Control and Countermeasure Act |上hai傲世皇朝3实验室设beiyou限公司
fang溢漏托pan

Spill Prevention, Control and Countermeasure Act

Intent
Driven by the EPA's Federal Water Pollution Control Act (as amended by the Clean Water Act), this ruling is designed to prevent discharges of oil and oil-related materials from reaching navigable waters and adjoining shorelines.
 

Background of the SPCC Act
The SPCC rule took effect on January 10, 1974. It was revised and strengthened in July of 2002. Parts of the original rule were unclear (i.e. container size was not specified) and compliance was expensive for small business due to the need to obtain certification by a Professional Engineer (PE).
 

Regulated Materials
Animal oils, fats and greases (including oils from fish or marine mammals), asphalt, aviation gasoline, bunker fuel, crude oil, cutting oil/machine coolants, dielectric fluid, diesel fuel, heating oil, gasoline, greases, hydraulic oil, jet fuel, lubricating oil, mineral spirits, motor oil, naptha, natural gas condensate, oil refuse, oily wastes (other than oil mixed with dredged soil), stoddard solvent, synthetic oils, tall oil, turpentine, residual fuels, used oil, vegetable oils (including oils from nuts, seeds, fruits and kernels). These materials are hereafter referred to as “oil” in this document.
 

Who must comply?
Facilities with total, above-ground, oil storage capacity (not actual gallons on site) of greater than 1,320 gallons. Storage containers that are 55-gallons and greater are used to calculate total capacity. Facilities with below-ground storage capacity of greater than 42,000 gallons must also comply. Facilities that meet such criteria must develop and implement a written SPCC Plan. Certain facility types, i.e., convenience stores, are exempt. In addition, EPA has extended compliance dates for four (4) problem areas: a) qualified, oil-filled operational equipment, b) motive power containers, c) mobile refuelers, and d) animal fats & vegetable oils at onshore & offshore oil production, drilling facilities.
 

What are the basics of an SPCC Plan?
The SPCC Plan must address all relevant spill prevention, control and countermeasures necessary to minimize the potential for oil discharge. One requirement is to provide appropriate containment and/or diversionary structures, i.e. dikes, berms or retaining walls, to prevent a discharge. A means of secondary containment sufficient to contain the capacity of the largest single compartment or container is mandated. Products that seal drains or divert spills from drains, as well as sorbents, are considered "control" or "countermeasures".
 

When is compliance required?
Compliance dates for facilities (other than farms) are as follows:
 

Copyright? 2003-2020  上hai傲世皇朝3实验室设beiyou限公司banquansuoyou
电hua:021-69106488 021-69106624 传真:021-69106489 地zhi:上haishi松江区广富林路658long3簆an醋致?410室 邮编:201620

huICPbei13012389号    

hu公网安bei 31011402005026号